Customization: | Available |
---|---|
Installation: | DIN Rail |
Application: | AC/DC System |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model Specification | LD-MD-20 | LD-MD-10 | ||||||||
Maximum Continuous Operating Voltage Uc (VAC) | 750 | 420 | 385 | 320 | 275 | 750 | 420 | 385 | 320 | 275 |
Voltage Protection Level Up (kV) ≤ | 2.5 | 1.8 | 1.5 | 1.4 | 1.2 | 2.0 | 1.6 | 1.3 | 1.2 | 1.0 |
Maximum Discharge Current (8/20μs) Imax (kA) | 20 | 10 | ||||||||
Nominal Discharge Current (8/20μs) In (kA) | 10 | 5 | ||||||||
Response Time (ns) | <25 | |||||||||
Protection Level | IP20 | |||||||||
Failure Indication | White indicates normal operation, and red indicates failure | |||||||||
Purpose | Three-level protection for the incoming line | |||||||||
Remote Signal Function | It can be additionally stocked | |||||||||
Ambient Temperature | -40ºC~+80ºC | |||||||||
Remarks | Other maximum continuous operating voltages Uc can be customized |
Model Specification | LD-MD-40 | |||||||
Maximum Continuous Operating Voltage Uc (VAC) | 100 | 7.5 | 420 | 385 | 320 | 275 | 175 | 48 |
Voltage Protection Level Up (kV) ≤ | 3.5 | 3.0 | 2.0 | 1.8 | 1.6 | 1.5 | 1.3 | 0.6 |
Maximum Discharge Current (8/20μs) Imax (kA) | 40 | |||||||
Nominal Discharge Current (8/20μs) In (kA) | 20 | |||||||
Response Time (ns) | <25 | |||||||
Protection Level | IP20 | |||||||
Failure Indication | White indicates normal operation, and red indicates failure | |||||||
Purpose | Three-level protection for the incoming line | |||||||
Remote Signal Function | It can be additionally stocked | |||||||
Ambient Temperature | -40ºC~+80ºC | |||||||
Remarks | Other maximum continuous operating voltages Uc can be customized |
Model Specification | LD-MD-60 | LD-MD-80 | |||||||
Maximum Continuous Operating Voltage Uc (VAC) | 1000 | 420 | 385 | 320 | 275 | 420 | 358 | 320 | 275 |
Voltage Protection Level Up (kV) ≤ | 4.0 | 2.2 | 2.0 | 1.8 | 1.6 | 2.5 | 2.2 | 2.0 | 1.8 |
Maximum Discharge Current (8/20μs) Imax (kA) | 60 | 80 | |||||||
Nominal Discharge Current (8/20μs) In (kA) | 30 | 40 | |||||||
Response Time (ns) | <25 | ||||||||
Protection Level | IP20 | ||||||||
Failure Indication | White indicates normal operation, and red indicates failure | ||||||||
Purpose | Three-level protection for the incoming line | ||||||||
Remote Signal Function | It can be additionally stocked | ||||||||
Ambient Temperature | -40ºC~+80ºC | ||||||||
Remarks | Other maximum continuous operating voltages Uc can be customized |