Customization: | Available |
---|---|
Type: | DC Combiner Box |
Structure: | Protection |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product model | HDLX-PV24 | HDLX-PV16 | HDLX-PV12 | HDLX-PV8 |
Number of input circuits | 17~24 | 13~16 | 8~12 | Less than 8 |
Maximum input voltage | 1000VDC | |||
Input current per circuit | 0~20A | |||
Maximum output current | 250A | 160A/200A | 100A/ 125A/160A | Less than 100A |
Input waterproof terminal size | PG9/PG11/MC4 | |||
Output waterproof terminal size | PG21~PG32 | PG19~PG25 | PG16~PG21 | PG13.5~PG19 |
Monitoring module | Detect each circuit current, bus voltage, breaker status, lightning protector status, and box temperature (optional) | |||
Communication mode/protocol | RS485 Bus / Standard MODBUS-RTU Protocol | |||
Anti-reflection function | Configure anti-reflection diode in modular package (optional) | |||
Temperature and humidity | Working temperature:-40 ~+85ºC , humidity 95%, no condensation, no corrosive gas | |||
Altitude | ≤ 4000m | |||
Monitoring module power consumption |
At work ≤ 8W | |||
Auxiliary power supply | AC85V~265V / DC24V(±10%) / DC200V~1000V | |||
Box material | Hot dip galvanized steel/stainless steel/cold rolled steel/engineering plastics | |||
The protection grades | P65 | |||
Volume (Length x height x width) | 850x500x200mm | 800x500x 180mm | 720x 500 x 180mm | 630x 500x 180mm |
Weight | 10~35kg |